Ventilation Calculations

Three calculations from the course. How many air changes an hour a blower gives you, what size blower a space needs, and how long to purge before anyone enters.

Always plan for a minimum of 7 air changes prior to entry.

Read this first. A practice tool, not an authority. Your entry permit, your gas monitor and your written procedure decide whether a space is safe to enter. Purge time is an estimate and must be extended for ducting length, bends in the ducting, and a flammable or toxic atmosphere.

Calculation 1

Air Changes per Hour

How many air changes an hour you get from a blower of a known capacity in a space of a known volume. Some entry procedures specify an ACH, typically 15 to 30.

Air Changes per Hour CFM × 60 ÷ VOL = ACH

Air Changes per Hour

CFM × 60 ÷ VOL

—

Air changes per hour

Worked examples from the course material
CFMVOL ACHLoad
8001100 43.64 (manual: 44)
12002900 24.83 (manual: 24.82)

10 CSE - Student Manual - V2.2 250519, section 3.5.3. Both rows are that section's Practice #1 and #2.

Calculation 2

Blower Capacity Needed

The other way round. Given the volume of the space and the air changes per hour your procedure requires, what size blower do you need?

Blower Capacity VOL × ACH ÷ 60 = CFM

A low hazard confined space requires at least 50 cfm of clean respirable air per worker, on top of whatever this gives you.

Blower Capacity

VOL × ACH ÷ 60

—

Blower capacity needed

Worked examples from the course material
VOLACH CFMLoad
230020 767 (manual: 766, use 800)
390025 1,625

10 CSE - Student Manual - V2.2 250519, section 3.5.3. Both rows are that section's Practice #1 and #2.

Calculation 3

Purge Time

How long to run the blower before entry. Two steps: air changes per minute first, then the time to reach the air changes you need.

Step 1 — Air Changes per Minute CFM ÷ VOL = ACM

Step 2 — Purge Time AC ÷ ACM = PTM

An estimate. Add time for ducting length, bends in the ducting, and the presence of a flammable or toxic atmosphere.

Always plan for a minimum of 7 prior to entry.

Step 1 — Air Changes per Minute

CFM ÷ VOL

Step 2 — Purge Time

AC ÷ ACM

—

Purge time

Worked examples from the course material
CFMVOLAC PTMLoad
57015007 18.4 min

10 CSE - Student Manual - V2.2 250519, section 3.5.3. The row is that section's Practice #1.